FDMET400

80SD2A00121

Natural gas detector fitted with base with relay output

The FDMET400 detectors allow to signal the presence of natural gas concentrations lower than the lower explosive limit (L.E.L.), i.e. 10%, long before an explosive mixture is composed. The detector is equipped with a relay alarm output with contact exchange (NO and NC), a malfunction output with optically isolated NC contact and two terminals to connect a power absorption line for conventional control units.
Supply voltage: 11 ÷ 29 VDC
Absorption at rest: 60mA at 12 VDC - 30mA at 24 VDC
Alarm absorption: 70mA at 12 VDC - 40mA at 24 VDC
Line alarm absorption: 50mA at 24 VDC
Delay for alarm: 20 seconds
Delay for alarm reset: 30 seconds
Alarm threshold for detection: 10% LEL – 0.50% in volume
Alarm relay output: (NO-NC) 1A, 30 VDC resistive load
Malfunction output: optically isolated NC contact 20mA, 30 VDC
Operating temperature: 0 ÷ 40°C (max* -15 ÷ 55°C)
Humidity: 30 ÷ 95% (max* 0 ÷ 95%)
Weight: 110g
White ABS casing
Protection class IP30
Dimensions Ø 90 x h 48 mm (base included)
User manuals
INSTALLATION AND USE MANUAL
DS80SD2A-001 | pdf | 86.20 KB | ID: 435047 | IT,EN,FR,ES | 11-06-2013
86.20 KB
CE Certification
Declaration of Conformity
CE_80177 | pdf | 856.89 KB | ID: 541070
856.89 KB
false

For further information about the product write us

Security-logo
Security

Security systems integrated technology, extended functionality

Pro-logo
Pro

Anti-intrusion solutions for complex systems

Fire-logo
Fire

Digital and conventional fire and gas detection systems

ARE YOU AN INSTALLER?

You can contact us at any time for technical assistance and more detailed documentation on all our security solutions.