Dual-technology detectors (smoke-heat) work according to the light scattering principle caused by smoke particles present in the air (TYNDALL effect) and on temperature monitoring within the area where they are installed. A micro controller analyses and compares the signal received from a precision heat detector of the NTC type, and activates the alarm if temperature goes over 58°C. The smoke detector features an automatic gain control function; a microcontroller calculates reading compensation to keep constant sensitivity.
Supply voltage: 20 Vdc (modulated voltage from -15% to + 10%)
Average absorption at rest: 65 μA @ 20 Vdc
Alarm absorption: 23 mA @ 20 Vdc
Static alarm threshold: 58° C ± 5%
3-colour LED: red alarm - green normal operation - yellow maintenance required - green
flashing with a sequence of yellow flashing system malfunction.
Minimum reset time: 300 mS
Max relative humidity: 93%
Operating temperature: -10° ÷ +55° C
Material: ABS V0
Weight: 70 g
Dimensions: ø 90 x 40 (H) mm
Certified EN54 part 5 class A1 and part 7, No. 1293-CPD-0178
User manuals
INSTALLATION AND USE MANUAL
DS80SD9U-001 | pdf | 149.25 KB | ID: 443110 | IT,EN | 27-02-2014
149.25 KB
CE Certification
Declaration of Conformity
CE_80021 | pdf | 558.55 KB | ID: 650675
558.55 KB
Quality Certification
Certificate
CCE80SD9U-001 | pdf | 2.92 MB | ID: 277163
2.92 MB
false

For further information about the product write us

Security-logo
Security

Security systems integrated technology, extended functionality

Pro-logo
Pro

Anti-intrusion solutions for complex systems

Fire-logo
Fire

Digital and conventional fire and gas detection systems

ARE YOU AN INSTALLER?

You can contact us at any time for technical assistance and more detailed documentation on all our security solutions.