Dual-technology detectors (smoke-heat) work according to the light scattering principle caused
by smoke particles present in the air (TYNDALL effect) and on temperature monitoring within
the area where they are installed. A micro controller analyses and compares the signal received
from a precision heat detector of the NTC type, and activates the alarm if temperature goes
over 58°C. The smoke detector features an automatic gain control function; a microcontroller
calculates reading compensation to keep constant sensitivity.
Supply voltage: 20 Vdc (modulated voltage from -15% to + 10%)
Average absorption at rest: 65 μA @ 20 Vdc
Alarm absorption: 23 mA @ 20 Vdc
Static alarm threshold: 58° C ± 5%
3-colour LED: red alarm - green normal operation - yellow maintenance required - green
flashing with a sequence of yellow flashing system malfunction.
flashing with a sequence of yellow flashing system malfunction.
Minimum reset time: 300 mS
Max relative humidity: 93%
Operating temperature: -10° ÷ +55° C
Material: ABS V0
Weight: 70 g
Dimensions: ø 90 x 40 (H) mm