The FDT100 heat detector detects the temperature in the protected area to promptly trigger the fire alarm and, at the same time, offers a high protection level against false alarms. The alarm condition occurs when the temperature or the thermal variation within a certain time frame exceeds the alarm threshold. In one of these conditions, an alarm message is sent to the MC100 module which reports it to the fire detection control unit connected to it. The alarm signal can reach the MC100 module directly or through one or more ESPMC100 addon modules. The communication between the input module and MC100 and ESPMC100 modules takes place in radio mode through a bidirectional protocol.
Distance of radio-communication with radio devices: 200 m (in free range)
Operating frequency 868 MHz
Modulation type FSK
Operating channels: 7
Power emitted 5 dBm (3mW) - typical value
Message transmission period 60 sec - Default value
Main battery: CR123A (3 VDC) type. Battery duration: 3 years in standard working condition
Secondary battery: CR123A (3 VDC) type. Average duration: 2 months
Dimensions 110 mm x 65 mm - Mounting base included
Weight 130 g - Mounting base included
Protection class IP21C
Maximum humidity 95% RH - Non condensing
Operating temperature -10°C ÷ +55°C
Compliant with EN54 standard part 5 and part 25
false