The MC100 module is a device that allows to interface a wireless fire detection system to a conventional or digital fire detection system. The MC100 module requires the wired connection to the control unit and the radio connection to all the field wireless devices. The module can be connected to the conventional detection control unit directly through the
absorption line and to the FAP digital system through the MC500 module item no. 80SC1E10121. The radio communication between the MC100 module and its accessories occurs throughbidirectional protocol. The module can be easily configured only from personal computer with“Wirelex Fire” software through RS232 serial connection.
Distance of radio-communication with radio devices: 200 m (in free range)
Operating frequency: 868 MHz
Modulation frequency: FSK
Operating frequency channels: 7
Radiated power emitted 5 dBm: (3mW)
Supply voltage: 9 Vdc ÷ 30 Vdc (typical 12 Vdc)
Minimum voltage threshold for power supply malfunction signal: 9 VDC
Applied voltage to conventional line of control unit: equal to supply voltage of the device
Maximum voltage of alarm warning line: 27 VDC
Maximum current consumption: 60 mA at 12 VDC (in alarm condition)
Operating temperature: -30°C to +50°C
Weight: 330 g
Dimensions (with antenna): (W x H x D) 190 x 230 x 50 mm
Dimensions (without antenna): (W x H x D) 120 x 160 x 50 mm
Protection class: IP51C
Software required for “Wirelex-Fire” system configuration, 5.0 revision or later
Compliant with EN54 standard part 25 and part 18