The MU100 output module is a battery-operated device that allows activation, switching and/or deactivation of electric circuits connected to its outputs. The activation/switching command is sent by the fire detection control unit through MC100 module or ESPMC100 module. The output module is provided with the following outputs: 12/24 VDC output and relay output in exchange. Communication between the input module and MC100 and ESPMC100 modules takes place in radio mode through a bidirectional protocol.
Distance of radio-communication with radio devices: 200 m (in free range)
Operating frequency: 868 MHz
Modulation frequency: FSK
Operating channels: 7
Power emitted: 5 dBm (3mW) typical value
Message transmission period 60 seconds - Preset period
Main battery: CR123A (3 VDC) type. Battery duration: 3 years in standard working condition
Secondary battery: CR123A (3 VDC) type. Average duration: 2 months
Protection class IP65
Preset for fairlead 6 x M16/20
Operating temperature -30°C ÷ +55°C - Relay output only
Operating temperature -10°C ÷ +55°C - 12/24 output set to 12 VDC
Operating temperature 0°C ÷ +55°C - 12/24 output set to 24 VDC
12/24 VDC: maximum output current 12 VDC (±10%): 40 mA
12/24 VDC: maximum output current 24 VDC (±10%): 20 mA
Relay output: maximum switching voltage: 30 VDC
Relay output: maximum switching current: 2 A
Relay output: maximum switching power: 60 W
Terminals - wire section 0.5 ÷ 2.5 mm
Compliant with EN54 standard part 25 and part 18
false